-40%

Whaley 25 ton circulating chiller RA25D-4-2P150T

$ 15840

Availability: 100 in stock
  • All returns accepted: ReturnsNotAccepted
  • Cooling Capacity: 25 ton
  • Brand: Whaley
  • Condition: Bought new, never installed.

    Description

    New price was ,526.
    Original quotation can be provided.
    Bought to chill large volumes of ethanol.
    Never installed.
    Located in Northern California.
    Packaged Air Cooled Chiller
    Model #: RA25D-4-2P150T
    Nominal Tons: 25 Ton (9.74 tons at -4F Leaving Glycol Temp (LGT), 95F(35C) Ambient,
    50% glycol)
    BTU/hr: 300,000 (116,960 BTU/hr at -4F Leaving Glycol Temp (LGT), 95F(35C) Ambient,
    50% glycol)
    Pump Configuration: Dual
    Voltage: 440-480/3ph/60hz
    Unit FLA : 73
    MCA: 91.25
    MOCP: 100.0
    Supply Pump HP: 5.0 HP
    Circ Pump HP: 2.0 HP
    Flow Rate: 60 gpm (can be revised if needed)
    Insulated Poly Tank Size: 150gal
    Length: 124"
    Width: 60"
    Height: 84"
    Shipping Weight: 2,640 lbs
    Number of Compressors: 2
    Inlet/Outlet Connections: 2”
    Unit Price: ,294.00 (excludes freight and options)
    Standard Features:
    • High Efficient R-404A Refrigerant
    • Copeland Scroll compressor(s)
    • Insulated stainless steel copper-brazed plate evaporator(s) (others available)
    • Cast iron end suction centrifugal supply pump rated at 2.4gpm per ton at 100’TDH (stainless
    available)
    • Insulated polypropylene reservoir with fill port and liquid level sight glass (larger volumes
    available)
    • Thermostatic expansion valve, filter drier, sight glass installed on refrigerant circuit(s)
    • Service ports and valves
    • NEMA 4 control panel with digital temperature controller
    • High and low pressure safety
    • Single point power connection
    Direct drive fan(s) made to run slower and more quiet
    • Air-Cooled vertical air discharge fans minimizes operating sound
    • Weather resistant fan motor made to survive in the elements.
    • Highly efficient coil provides excellent heat transfer and low air resistance
    • Energy Star qualified unit
    • Assembled, plumbed, and wired on industrial epoxy-coated steel frame
    • Refrigerant circuit(s) pressure tested for leaks with nitrogen charge
    • Refrigerant circuit(s) vacuum tested for leaks to negative-psi pressure
    • Refrigerant circuit(s) fully charged with refrigerant
    • Hydronic circulation loop leak tested under full flow using the WHALE-SOFT™ Testing Platform.
    • Complete systems fully run tested under heat load using the WHALE-SOFT™ Testing Platform